TAYLOR COUNTY BUILDING DEPARTMENT
![]()
(Consult with power company serving site about pole
location)
Minimum diameter of 5 inches at top of pole. Weatherhead within 2 foot of top of pole. SERVICE CONDUCTOR
SIZES (TO MOBILE HOME) COPPER 100 AMP 150 AMP 200 AMP HOT # 4 # 1 2 / 0 NEUTRAL # 6 # 2 1 / 0 GROUND # 8 # 6 # 6 ALUMINUM
(anti-corrosion compound must be used) 100 AMP 150 AMP 200 AMP HOT # 2 2 / 0 4 / 0 NEUTRAL # 4 1 / 0 2 / 0 GROUND # 6 # 4 # 4 MOBILE HOME
SERVICE EQUIPMENT 1. Feeder to mobile home must consist of 4
wires. (2 hots, 1 neutral, 1
ground) 2. Must
have a main breaker if more than a 6 circuit panel. 3. 100
amp homes fed from a 200 amp panel
must have a 100 amp breaker installed in the outside panel. 4. Backfed
main breakers must be secured in place. 5. Power
pole must be within 30 feet of mobile home. 6. Neutral
and ground in home do not go to
the same bus. Ground (4th)
wire should go to the ground bus (one with the bare / green wires on it). 7. Wiring
under home must be in conduit (PVC is acceptable) and be strapped to the
mobile home frame. Conduit run on
ground will not be approved. 8. All
unused openings in panel must be closed with hole plugs or panel
blanks. Tape will not be accepted. 9. Receptacles
on pole must be GFCI protected.
(110 volt, 15 or 20 amp) Straps required Within 36 inches of meter And not more than 5 feet Apart thereafter 15
feet
5 ½ feet # 4 solid copper ground ground rod 8 feet long 5
feet
![]()
![]()
![]()
![]()
![]()
![]()
![]()
Burial depth 18 inches if in PVC. 24 inches for direct burial wire (must
be in conduit down to 18 inches below grade). White PVC is not acceptable below ground.